MSR — Motion Set/Redefine Position

Category
Motion
Type
Output
Availability
Stepper and servo axes (Explorer ▸ Axes); not allowed on a DC axis

MSR instruction block: a block labelled MSR with rows Axis: Feed and Redefine: 0


MSR (Motion Set/Redefine Position) tells an axis where it is. On the false-to-true transition of its rung the axis position is set to the Position operand without any motion: ActualPos, CmdPos and Counts take the new value, RedefinePos records it, and DN and PC set. Any move in progress is cancelled. Use MSR at a home sensor to establish the machine zero, to re-home after a hand move, or to zero the counter at power-up. Do not use MSR to move an axis; nothing turns. Use MAM for that.


Operand Type Format Valid Range Required Description
Axis Axis Axis name Any stepper or servo axis with a driver Yes The axis to redefine.
Position REAL Literal or tag Any value in axis units Yes The value the current position becomes. A tag is read on the edge.

Nothing. The edge memory starts false, so a rung already true on the first scan redefines on that scan.

Nothing. The edge memory is armed.

On the rising edge only: the axis’s current position and its target are both set to Position, so no move results; Counts = Position × counts per unit; ActualPos = CmdPos = RedefinePos = Position; DN = PC = 1. A move that was running stops where it is. Further true scans do nothing.

Nothing.

Before After the edge
ActualPos = 174 (wherever the axis was) ActualPos = Position
Counts = 13920 Counts = Position × counts per unit
DN = 0 DN = 1, PC = 1
Move in progress Cancelled, axis at rest

Motion status lives on the axis, not on a per-instruction tag.

Member Data type Set by Cleared by Description
RedefinePos REAL MSR — Value of the last MSR. This member exists for MSR.
ActualPos REAL MSR, axis service every scan — Position in axis units.
CmdPos REAL MSR, MAM, MAG — Commanded target in axis units.
Counts DINT MSR, axis service every scan ResetCounts Raw step counts.
DN BOOL MSR, MAM reaching its target Next MAM or MAJ Instruction done.
PC BOOL Same as DN Same as DN Process complete.
EN BOOL MAM, MAJ, MAG while a command is active Command complete, MAS, MSF A motion command is engaged. Not set by MSR.
IP BOOL Axis service while steps are being produced Motion stops Motion in process.
InMotion BOOL Axis service Axis service Steps produced this scan.
Dir BOOL Axis service Axis service 1 = forward.
DriverOn BOOL MSO MSF The drive is enabled. MSR works with the drive on or off.
Error BOOL Watchdog mismatch, TMC2130 driver fault MAFR Axis fault.
ResetCounts BOOL Your logic (write 1) Firmware, after zeroing Zero the counts without an MSR; the same as MSR 0.
Watchdog INT (ms) Axis properties; your logic may overwrite — Mismatch tolerance before Error sets.

Scenario: A set-home pushbutton declares the Feed carriage’s current position to be 0 mm, after the operator has jogged it against the reference stop.

Tags:

  • Set_Home — Set home position, BOOL
  • Feed — stepper axis, 80 counts per mm

Rung 1:

—|XIC Set_Home|———[MSR Feed Redefine 0]———

Scan 1 — Set_Home = 0. The carriage sits at 174 mm after the jog on the MAJ page: Feed.ActualPos = 174.

Figure 1 — MSR rung false: Set_Home off, wire dark, the block showing Redefine 0

Scan 2 — Set_Home = 1 (rising edge). Nothing moves. Feed.ActualPos = 0, Feed.Counts = 0, Feed.RedefinePos = 0, Feed.DN = 1.

Figure 2 — MSR rung true: Set_Home on, the wire lit through the block

Values before and after: Feed.ActualPos 174 → 0 with the motor standing still. Every absolute MAM from now on is measured from this spot.


  • MAM — Motion Axis Move (absolute moves need a home)
  • MAJ — Motion Axis Jog (find the home sensor)
  • MSF — Motion Servo Off (re-home after a hand move)
  • Motion Instructions — Category index

Homing pattern. XIC Home_Sw → MSR Feed 0 on its own rung, with the jog toward the switch on another. The MSR fires on the scan the switch closes and cancels the jog’s pending target; release the jog button and the axis is homed.

ResetCounts is the short form. Writing 1 to <axis>.ResetCounts from an OTE zeroes the counts on the next scan and the bit clears itself. MSR does the same for any value and records it in RedefinePos.

Not a move. Redefining to 100 when the axis is at 0 does not send it anywhere. A following absolute MAM to 100 would then do nothing.

Geared followers. MSR on a master axis changes the master’s position, so a follower geared to it drives to the new master × Ratio.

Servo axis. MSR sets the reported angle without moving the horn; the physical servo stays where the last MAM put it.

Applies to LadderIDE >=1.2.2 · Last reviewed 2026-09-11 · Screenshots verified 2026-09-11